XM31-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V1.04.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 122.88 V
Current 7.00 A
Power 729 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 8,573 Wh
Output
Voltage 87.61 V
Power 595 W
Apparent Power 682.48 VA
Frequency 60.05 Hz
Percent Load 43.20 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 7.79 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 106
Time Since Last Standby Event 19d 10h:15m
Time in Last Standby Event 0d 3h:29m
Total Time in Standby 1,279 min
Standby Events Since Reset 30
Time in Standby Since Reset 468 min
Time Since Reset 1,289 day(s)
Total Run Time 1,289 day(s)
Transformer Run Time 1,289 day(s)
Total Downtime 0d 15h:28m
Oil Cap Lifespan Consumed 64.4 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 30 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 